|
Opinions Archive
Electrical
|
Q: Which electrical code should be used, the current IRC or the current NEC?
A: When the IRC code was adopted by the Texas Legislature and signed by Governor Perry into
law as the state wide building code, the IRC electrical section was replaced by the current
NEC (National Electrical Code). The bill also states that you are to use the "current" NEC
code statewide. A municipality may alter the code to make it more stringent, but cannot alter
it to be less stringent than the current code. As of this writing, the current NEC code is the
2005 edition. (Read more...)
Equipment Locations
Q: What are the accessibility requirements for A/C condensing unit disconnects?
A: A/C condensing unit disconnects are not allowed to be installed behind the condenser. There
must be a minimum of a 30" wide space directly in front of the disconnect. It does not have to
be centered on the disconnect and can fall anywhere within this 30" space. (Read more...)
Outlet Placement
Q: Can an electrical outlet located in a garage not have GFCI protection if it is dedicated for an
irrigation system?
A: Yes. The National Electrical Code states clearly in 210.8 (A) (2) Exception No. 2. However,
this exception is being voted on, and may not be in the 2008 NEC. If voted out, this would no
longer be allowed. It is worth noting that the intent of requiring GFCI outlets inside a garage is
to prevent anyone from using an electrical appliance outside the home without GFCI
protection. Care should be taken to either cover unprotected outlets or locate them in a
location that indicates they are dedicated. (Read more...) |